*Maximum outlet temperature and ambient range are separate limits; confirm the operating envelope.
| Availability: | |
|---|---|
Choose from three listed capacity classes for central hot-water projects. At the stated standard test condition, heating outputs are 52, 75 and 115 kW.
Compare hotel, accommodation and shared-facility demand by project.
Select against peak draw-off, recovery time and storage volume.
Capacity varies with air and water conditions.
The specification lists a maximum outlet water temperature of 70°C for all three models. This supports evaluation of higher-temperature hot-water requirements.
Standard performance is rated for water heating from 15 to 55°C.
Maximum outlet temperature is separate from the rated performance point.
Confirm the permitted temperature at the project design ambient.
All three columns specify Hitachi inverter compressors. Standard-condition COP values are 4.65 for the 50 kW class and 4.25 for the 75 and 115 kW classes.
Compare heating input and output at the same test condition.
Rated heating input: 11.18 / 17.65 / 27.10 kW.
Project consumption depends on operating conditions and demand.
The declared ambient operating range is −15 to 45°C. Separate air 7/6°C and −7/−8°C ratings help assess capacity at colder design points.
At air −7/−8°C: 27.61 / 43.71 / 85.42 kW heating output.
The low-temperature test heats water from 9 to 55°C.
Do not apply standard-condition output to minimum ambient.
The listed water-side heat exchanger is coaxial. Connection sizes, rated flow, unit weight and dimensions are provided separately for each capacity class.
Connections: DN40 / DN50 / DN65.
Maximum water pressure: 1.0 MPa; enclosure rating: IPX4.
Check access, structural loading and top-discharge clearance.
Share peak demand, storage volume, climate and target water temperature.
Air temperatures are dry-bulb / wet-bulb (DB/WB). Water temperatures show the heating interval. Scroll horizontally on small screens.
| Capacity | 50kW | 75kW | 100kW | |||
| Model | GHWVTV-50AA1 | GHWVTV-75AA1 | GHWVTV-115AA1 | |||
| General Specifications | ||||||
| AC Power Supply (V / Ph / Hz) | 380 / 3 / 50 | |||||
| Operating Ambient Temperature (°C) | −15~45 | |||||
| Maximum Leaving-Water Temperature (°C) | 70 | |||||
| Heating Performance · Air DB 20 °C, WB 15 °C / Water inlet 15 °C, outlet 55 °C | ||||||
| Heating Capacity (kW) | 52.00 | 75.00 | 115.00 | |||
| Electrical Power Input (kW) | 11.18 | 17.65 | 27.10 | |||
| Coefficient of Performance (COP) | 4.65 | 4.25 | 4.25 | |||
| Norminal Hot Water Output (L) | 1118 | 1612 | 2472 | |||
| Heating Performance · Air DB 7 °C, WB 6 °C / Water inlet 9 °C, outlet 55 °C | ||||||
| Heating Capacity (kW) | 38.45 | 54.50 | 106.50 | |||
| Electrical Power Input (kW) | 10.36 | 15.35 | 30.00 | |||
| Coefficient of Performance (COP) | 3.71 | 3.55 | 3.55 | |||
| Norminal Hot Water Output (L) | 719 | 1019 | 1991 | |||
| Heating Performance · Air DB -7 °C, WB -8 °C / Water inlet 9 °C, outlet 55 °C | ||||||
| Heating Capacity (kW) | 27.61 | 43.71 | 85.42 | |||
| Electrical Power Input (kW) | 11.27 | 18.60 | 36.35 | |||
| Coefficient of Performance (COP) | 2.45 | 2.35 | 2.35 | |||
| Electrical & Refrigerant Specifications | ||||||
| Rated Electrical Power Input (kW) | 13.50 | 19.30 | 40.00 | |||
| Rated Input Current (A) | 30.50 | 35.50 | 74.00 | |||
| Refrigerant Type / Charge / Declared GWP | R290 / 2.50 kg / 3 | R290 / 3.80 kg / 3 | R290 / 2.50 kg*2 / 3 | |||
| Rated Water Flow (m³/h) | 8.80 | 13.00 | 22.90 | |||
| Water Pressure Drop (MPa) | 1.00 | 1.00 | 1.00 | |||
| Water Connection | DN40 | DN50 | DN65 | |||
| Acoustic Data | ||||||
| Noise Level at 1 m [dB(A)] | 40~64 | 40~66 | 40~68 | |||
| Dimensions & Shipping | ||||||
| Net Weight (kg) | 160 | 450 | 1080 | |||
| Unit Dimensions (mm) | 1210×453×1650 | 1110×1110×2150 | 2000×1110×2250 | |||
The maximum water temperature and minimum ambient are separate listed limits. The source does not establish 70°C output at −15°C ambient. Obtain the complete operating envelope for the ordered version.
The noise row does not identify sound pressure / sound power, distance or test condition; do not describe it as a 1 m sound-pressure rating. The source hot-water-output rows are labeled only “L”, with no time basis: they are excluded from rate claims pending clarification.
Why is the 50 kW class shown as 52 kW?
The workbook labels the model column “50KW” and separately declares 52 kW at air 20/15°C with water heated from 15 to 55°C. Both are retained without treating the capacity label as an order code.
Can the unit deliver 70°C at −15°C ambient?
The sheet lists these as separate limits. It does not supply the full water/ambient envelope. Confirm the permitted outlet temperature at the project design point.
How should I compare the COP values?
Use the same air DB/WB and water heating interval. Standard-condition COP is 4.65 / 4.25 / 4.25; colder-condition values appear separately in the parameter table.
Does this page include a PV direct-driven version?
The available specification does not establish PV direct drive for this product. Request a confirmed configuration and its dedicated electrical data if needed.
Can the products be controlled in a cascade?
Cascade functions, maximum unit count and communications are not confirmed in the supplied files. Obtain the project control specification before including them in a design.
How much hot water can it produce per hour?
The source hot-water-output rows provide litres without a defined time basis. An hourly rate requires confirmed conditions and manufacturer data; it is not inferred on this page.
Does a rendering identify the exact ordered cabinet?
The image folder contains multiple cabinet views, while the sheet supplies three dimension sets. Confirm the rendering, outline drawing and order code together before finalizing the project.
Share peak demand, storage volume, climate and target water temperature.